川消水泵接合器設置場所以及安裝要求
來源:http://m.xintli.net/ 日期:2022-07-31
設置場所
Setting place
下列場所的室內消火栓給水系統應設置消防水泵接合器:
The indoor fire hydrant water supply system in the following places shall be equipped with fire pump adapters:
1. 高層建筑;
1. High rise buildings;
2. 設有消防給水的住宅、超過五層的其他多層民用建筑;
2. Houses with fire water supply and other multi-storey civil buildings with more than five floors;
3. 超過四層的多層工業建筑;
3. Multi storey industrial buildings with more than four floors;
4. 超過2層或建筑面積大于10000㎡的地下或半地下建筑(室);
4. Underground or semi underground buildings (rooms) with more than 2 floors or a building area of more than 10000 m2;
5. 室內消火栓設計流量大于10L/s平戰結合的人防工程;
5. Civil air defense works with the design flow of indoor fire hydrant greater than 10l/s and the combination of peacetime and wartime;
6. 城市交通隧道。
6. Urban traffic tunnel.
7. 自動噴水滅火系統、水噴霧滅火系統、泡沫滅火系統和固定消防炮滅火系統等水滅火系統,均應設置消防水泵接合器。
7. Automatic sprinkler system, water spray fire extinguishing system, foam fire extinguishing system, fixed fire monitor fire extinguishing system and other water extinguishing systems shall be equipped with fire pump adapters.
8. 4層以上的多層汽車庫、高層汽車庫和地下、半地下汽車庫,其室內消防給水管網應設置水泵接合器;
8. For multi-storey garages, high-rise garages, underground and semi underground garages with more than 4 floors, their indoor fire water supply network should be equipped with water pump adapters;
9. 在地下車站出入口或新風亭的口部等處明顯位置應設水泵接合器;
9. A water pump adapter should be set at the obvious position at the entrance and exit of the underground station or the entrance of the fresh air Pavilion;
10. 設置室內消防給水系統的在建工程。
10. Construction in progress of setting indoor fire water supply system.

安裝要求:
Installation requirements:
1.
川消消防水泵接合器應設置在室外便于消防車取水的部位,與室外消火栓或消防水池取水口的距離宜為 15m~40m。
1. The fire water pump adapter of Chuanxiao should be set at the outdoor position convenient for fire engines to take water, and the distance from the outdoor fire hydrant or the water intake of the fire pool should be 15m ~ 40m.
2. 水泵接合器與給水系統之間不應設置除檢修閥門以外的其他閥門,且檢修閥門應在水泵接合器周圍就近設置,且應保證便于操作。
2. No valve other than the maintenance valve shall be set between the pump adapter and the water supply system, and the maintenance valve shall be set nearby the pump adapter to ensure easy operation.
3. 當水泵接合器的供水能力不能滿足不利點處作用面積的流量和壓力要求時,應采取增壓措施。
3. When the water supply capacity of the pump adapter cannot meet the flow and pressure requirements of the action area at the adverse point, pressurization measures should be taken.
4. 消防水泵接合器的給水流量宜按每個10~15L/s,設置的數量按系統設計流量計算確定,當超過3個時,可根據供水可靠性適當減少。等等。
4. The water supply flow of the fire pump adapter should be 10 ~ 15l/s each, and the number of settings should be calculated and determined according to the system design flow. When there are more than 3, it can be appropriately reduced according to the water supply reliability. wait.