1、檢查閥瓣上橡膠墊片的密封面,附著在橡膠密封墊上的污物和異物;橡膠密封件使用壽命一般在十八個月內,若有磨損、老化,應及時更換。
1. Check the sealing surface of the rubber gasket on the valve disc and remove the dirt and foreign matters attached to the rubber gasket; The service life of rubber seal is generally within 18 months. If there is wear and aging, it should be replaced in time.
2、半年檢查一次流動水壓,檢查時打開放水閥,警鈴發出報警聲響,此時,壓力表所顯示的壓力值不應明顯下降,如果下降較為顯著,應檢查閘閥是否堵塞或未開;如果壓力表所顯示的壓力下降比較明顯,且警鈴不報警,應檢查濕式報警止回閥的閥瓣啟動是否正常。
2. Check the flowing water pressure once a half year. Open the drain valve and the alarm bell will sound. At this time, the pressure value displayed on the pressure gauge should not drop significantly. If the drop is significant, check whether the gate valve is blocked or not opened; If the pressure drop shown on the pressure gauge is obvious and the alarm bell does not alarm, check whether the valve disc of the wet alarm check valve is started normally.
3、應半月檢查一次警鈴轉動是否正常,檢查時打開放水閥,報警閥瓣因水壓差而自動打開,水流入延遲器經20-30秒后,警鈴發出報警聲響。
3. Check whether the alarm bell rotates normally once every half a month. Open the drain valve during the inspection. The alarm valve flap will open automatically due to the water pressure difference. After 20-30 seconds, the alarm bell will sound.
如果警鈴不發出響聲,應檢查整個警鈴管道,排除其水垢、泥沙及污物,使水流暢通,防止報警失靈。若警鈴校驗旋塞關閉后,警鈴仍發聲,則應檢查校驗旋塞是否關緊、在報警閥的環形水槽上是否積聚了障礙物、報警閥瓣下的橡膠是否老化或皺褶。使用iFire消防寶處理日常為保,準確掌握設備信息,對這些故障應及時排除。
If the alarm bell does not sound, check the entire alarm bell pipe to remove its scale, sediment and dirt, so as to make the water flow smooth and prevent alarm failure. If the alarm bell still sounds after the alarm bell check cock is closed, check whether the check cock is closed tightly, whether obstacles are accumulated on the annular water tank of the alarm valve, and whether the rubber under the alarm valve flap is aging or wrinkled. Use ifare fire protection treasure to handle daily affairs, accurately grasp equipment information, and timely eliminate these faults.

4、每年應檢查一次密封件和閥座密封圈環形槽內的小孔和密封面,污物或異物;密封面不應劃傷,小孔保持通暢,不能修復應予更換。
4. Check the small holes and sealing surfaces in the annular groove of the sealing element and valve seat sealing ring once a year to remove dirt or foreign matters; The sealing surface shall not be scratched, and the small hole shall be kept unobstructed. If it cannot be repaired, it shall be replaced.
5、根據消防用水的水質情況,定期打開過濾器上排污口,清理臟物,保持管路通暢。
5. According to the water quality of fire water, regularly open the drain outlet on the filter, clean the dirt and keep the pipeline unblocked.
6、檢查和清理延遲器內的臟物,節流小孔不應有異物堵塞。
6. Check and clean the dirt in the retarder, and the throttle orifice shall not be blocked by foreign matters.
7、日常注意消防水池的水位及水壓和相應閥門所處狀態是否符合規范要求。
7. Daily attention shall be paid to whether the water level and pressure of the fire pool and the state of the corresponding valves meet the specification requirements.
看完小編對濕式報警閥的日常維護注意事項的介紹,是不是已經知道要怎么去維護它了呢?看完介紹是不是就覺得很簡單了呢,那還在等什么,趕緊行動吧。更多注意事項就來我們網站
http://m.xintli.net咨詢吧!
After reading Xiaobian's introduction to the daily maintenance precautions of the wet alarm valve, do you know how to maintain it? After reading the introduction, do you think it is very simple? What are you waiting for? Hurry up. For more information, please visit our website http://m.xintli.net Consult!