消防水泵接合器設置及安裝要求
來源:http://m.xintli.net/ 日期:2022-08-31
一般水泵接合器的使用方法是直接把水泵接合器的閥門打開,連接消防水帶,直接加壓供水,多用式水泵接合器使用時需要把進水閥口打開,再把旋轉閥門打開方可向管網內供水。下面
川消小編為您講講消防水泵接合器設置及安裝要求。
Generally, the use method of the water pump adapter is to directly open the valve of the water pump adapter, connect the fire hose, and directly pressurize the water supply. When the multi-purpose water pump adapter is used, it needs to open the inlet valve and then open the rotary valve to supply water to the pipe network. Next, Chuanxiao Xiaobian will tell you about the setting and installation requirements of the fire pump adapter.
1.消防水泵接合器應設置在室外便于消防車取水的部位,與室外消火栓或消防水池取水口的距離宜為15m~40m。
1. The fire pump adapter shall be set at the outdoor position convenient for the fire truck to take water, and the distance from the outdoor hydrant or the water intake of the fire pool should be 15m-40m.
2.水泵接合器與給水系統之間不應設置除檢修閥門以外的其他閥門,且檢修閥門應在水泵接合器周圍就近設置,且應保證便于操作。
2. No valves other than maintenance valves shall be set between the pump adapter and the water supply system, and the maintenance valves shall be set nearby the pump adapter and shall be easy to operate.
3.當水泵接合器的供水能力不能滿足不利點處作用面積的流量和壓力要求時,應采取增壓措施。
3. When the water supply capacity of the water pump adapter cannot meet the flow and pressure requirements of the action area at the unfavorable point, pressure boosting measures shall be taken.
4.消防水泵接合器的給水流量宜按每個10~15L/s,設置的數量按系統設計流量計算確定,當超過3個時,可根據供水可靠性適當減少。
4. The water supply flow of the fire pump adapter should be 10-15l / s each, and the number of settings should be determined according to the system design flow. When there are more than 3, it can be appropriately reduced according to the water supply reliability.

5.安裝順序組裝式消防水泵接合器的安裝應按接口、本體、聯接管、止回閥、閥、放空管、控制閥的順序進行,止回閥的安裝方向應使消防用水能從消防水泵接合器進入系統。整體式消防水泵接合器的安裝應按其使用安裝說明書進行。
5. Installation sequence: the assembled fire pump adapter shall be installed in the order of interface, body, connecting pipe, check valve, safety valve, vent pipe and control valve. The installation direction of the check valve shall enable the fire water to enter the system from the fire pump adapter. The installation of the integral fire pump adapter shall be carried out according to its operation and installation instructions.
6.墻壁式消防水泵接合器安裝高度距地面宜為0.7m,與墻面上的門、窗、孔、洞的凈距離不應小于2.0m,不應安裝在玻璃幕墻下,水泵接合器性標志銘牌底部距室外地坪0.9m
6. The installation height of the wall type fire pump adapter should be 0.7m from the ground, and the net distance from the door, window, hole and hole on the wall should not be less than 2.0m. It should not be installed under the glass curtain wall. The bottom of the permanent mark nameplate of the water pump adapter should be 0.9m from the outdoor floor
7.地下式消防水泵接合器進水口與井蓋底面的距離不大于0.4m,且不小于井蓋的半徑。
7. The distance between the water inlet of the underground fire pump adapter and the bottom surface of the well cover shall not be greater than 0.4m and not less than the radius of the well cover.
水泵接合器是由閥門、閥、止回閥、栓口放水閥以及聯接彎管等組成。水泵接合器的組件排列次序應合理,從給水方向,依次是栓口放水閥、止回閥、閥、閥門。更多相關內容您可以來我們網站
http://m.xintli.net進行咨詢!
The pump adapter is composed of a valve, a safety valve, a check valve, a drain valve at the bolt mouth and a connecting elbow. The components of the pump adapter shall be arranged in a reasonable order. From the direction of water supply, they are the outlet drain valve, check valve, safety valve and valve. You can visit our website for more information http://m.xintli.net Consult!