現(xiàn)在,大空間場所安裝使用自動消防水炮的情況越來越多,不過對于大空間場所來說,自動消防炮滅火系統(tǒng)的選型一直都是客戶考慮的問題之一。因?yàn)樾吞栠x對了,有可能涉及的數(shù)量可以優(yōu)化到少。那么具體在選擇型號的時候,是否有規(guī)范可依,或者應(yīng)該怎么來選擇呢?這個問題
川消小編今天來給大家好好講解一下。
At present, there are more and more automatic fire monitors installed and used in large space places. However, for large space places, the selection of automatic fire monitor fire extinguishing system has always been one of the key considerations of customers. Because the model is selected correctly, the number involved may be minimized. Is there any specification to follow or how to choose the model? This is a question that Chuanxiao Xiaobian will give you a good explanation today.
其實(shí),在國標(biāo)《自動跟蹤定位射流滅火系統(tǒng)技術(shù)標(biāo)準(zhǔn) 51427-2021》中第4.2.2中明確規(guī)定了:自動消防炮滅火系統(tǒng)用于撲救民用建筑內(nèi)火災(zāi)時,單臺炮的流量不應(yīng)小于20L/s;用于撲救工業(yè)建筑內(nèi)火災(zāi)時,單臺炮的流量不應(yīng)小于30L/s。
In fact, in the national standard Technical Standard for Automatic Tracking and Positioning Jet Fire Extinguishing Systems 51427-2021, 4.2.2 clearly stipulates that when the automatic fire monitor fire extinguishing system is used to put out fires in civil buildings, the flow of a single monitor shall not be less than 20L/s; When it is used to put out a fire in an industrial building, the flow of a single monitor shall not be less than 30L/s.
什么是自動消防炮滅火系統(tǒng)呢?這個之前也跟大家詳細(xì)解答過,就是流量超過16L/s的稱之為自動消防炮滅火系統(tǒng)。上述4.2.2規(guī)范是強(qiáng)制性條文,須嚴(yán)格執(zhí)行。
What is an automatic fire monitor fire extinguishing system? This has also been explained to you in detail before. It is called automatic fire monitor fire extinguishing system if the flow exceeds 16L/s. The above 4.2.2 specifications are mandatory and must be strictly implemented.

也就是說,如果確定大空間場所安裝自動消防炮滅火系統(tǒng)的時候,不管是選型還是圖紙設(shè)計,實(shí)際上只有20L和30L兩種規(guī)格考慮,而且國標(biāo)中也已經(jīng)做出了明確的選型劃分。
That is to say, when it is determined to install automatic fire monitor fire extinguishing system in large space, no matter in terms of model selection or drawing design, only 20L and 30L specifications are considered in fact, and clear model selection division has been made in the national standard.
民用建筑選擇20L/s的規(guī)格就可以,而工業(yè)建筑則需要選擇30L/s的規(guī)格。那么,哪類建筑屬于民用建筑或者民用建筑包括哪些場所呢?這里給大家簡單的匯總了一下。
For civil buildings, the specification of 20L/s is acceptable, while for industrial buildings, the specification of 30L/s is required. So, which kind of buildings belong to civil buildings or which places are included in civil buildings? Here is a brief summary.
民用建筑的定義是:非生產(chǎn)性的居住建筑和公共建筑,比如說、電影院、會展中心、醫(yī)院、體育場館、客運(yùn)站等都屬于。這些場所如果確定要安裝自動消防炮滅火系統(tǒng)的話,那么選型上就是20L/s的規(guī)格就可以了,當(dāng)然也可以根據(jù)現(xiàn)場環(huán)境空間的大小來選擇30L/s。
Civil buildings are defined as non productive residential buildings and public buildings, such as shopping malls, cinemas, exhibition centers, hospitals, stadiums, passenger stations, etc. If the automatic fire monitor fire extinguishing system is determined to be installed in these places, the model selection is 20L/s, and of course, 30L/s can also be selected according to the size of the on-site environmental space.
工業(yè)建筑的定義就與民用建筑相反了,比較常見的像工廠車間、成品倉庫、生產(chǎn)廠房等都屬于,這些場所在安裝自動消防炮滅火系統(tǒng)的時候,型號只能選擇30L/s的,不能選擇20L/s規(guī)格的,這一點(diǎn)要嚴(yán)格按照國標(biāo)規(guī)范來才行。更多相關(guān)內(nèi)容就來我們網(wǎng)站
http://m.xintli.net咨詢吧!
The definition of industrial buildings is opposite to that of civil buildings. The more common ones, such as factory workshops, finished product warehouses, and production plants, belong to. When installing automatic fire monitor fire extinguishing systems in these places, the model can only be 30L/s, not 20L/s, which should be strictly in accordance with the national standards. More relevant content will come to our website http://m.xintli.net Consult!