Hand lift motorized fire pump (referred to as hand lift pump) refers to a fire pump that is assembled with a light engine and can be moved manually. As an independent water supply unit, hand pump has wide applicability, strong mobility and sometimes can play a role that cannot be replaced by fire engines. Next, Sichuan Xiaobian will talk about the operation of hand-held motor fire pump and the maintenance after pumping.
手抬機動消防泵的操作
Operation of manually driven fire pump
1.啟動泵前,請先關(guān)閉出水閥門和排余水閥;
1. Before starting the pump, please close the outlet valve and drain valve;
2.使用消防栓、消防水罐或串聯(lián)供水時,請始終保持入水口閥門關(guān)閉;
2. When using fire hydrants, fire water tanks or series water supply, always keep the inlet valve closed;
3.從開放的水域取水時,請完全打開入水口閥門;
3. When taking water from open waters, please fully open the water inlet valve;
4.將油門加壓到指定位置,形成吸力;
4. Press the accelerator to the specified position to form suction;
5.請勿操作真空泵長于45秒.若泵為成功出水,即為故障;
5. Do not operate the vacuum pump for more than 45 seconds. If the pump successfully discharges water, it is a fault;
6.無水空轉(zhuǎn)周期不超過2分鐘;
6. Dry idling period shall not exceed 2 minutes;
7.穩(wěn)定的加快和減緩發(fā)動機速度;
7. Stable acceleration and deceleration of engine speed;
8.定期觀察儀表,確保設(shè)備正常運轉(zhuǎn);
8. Regularly observe the instrument to ensure the normal operation of the equipment;

9.使用入水口抽水時,常遇到的問題是入水口露出水面,導(dǎo)致無法形成真空;
9. When using the water inlet to pump water, the problem often encountered is that the water inlet is exposed to the water surface, resulting in the inability to form a vacuum;
10.從開放區(qū)域抽水時,一定要使用過濾器;
10. When pumping water from an open area, be sure to use a filter;
11.常見發(fā)生的故障,葉輪被吸入的異物纏繞;
11. Common faults, impeller is entangled by foreign matters inhaled;
12.每次使用后,請即刻將泵內(nèi)余水排空;
12. After each use, please drain the remaining water in the pump immediately;
13.每次抽水后,請檢查發(fā)動機各個油量及使用狀況;
13. After pumping water each time, please check the oil volume and service condition of the engine;
14.出水閥門完全關(guān)閉時,請勿使設(shè)備長時間空轉(zhuǎn)。
14. When the outlet valve is completely closed, do not idle the equipment for a long time.
15.油門加速抽水時,請勿長時間關(guān)閉出水閥門。
15. Do not close the water outlet valve for a long time when the accelerator is accelerating to pump water.
手抬機動消防泵抽水后的維護
Maintenance after pumping by hand driven fire pump
抽水結(jié)束后:
After pumping:
1.立刻將泵體內(nèi)的余水排出。(排水閥在泵體低處)。
1. Discharge the residual water in the pump immediately. (The drain valve is at the lower part of the pump body).
2.泵體排空后,切記關(guān)閉排水閥,否則下次使用無法形成真空;
2. After the pump body is emptied, be sure to close the drain valve, otherwise a vacuum cannot be formed in the next use;
3.不常用的消防泵應(yīng)保持定期檢查和使用,確保緊急情況時隨時可用,每周定期啟動;
3. The fire pump not in common use shall be checked and used regularly to ensure that it is available at any time in case of emergency, and it shall be started regularly every week;
4.如抽咸水或者臟水,建議用清水清洗泵內(nèi)葉輪等。
4. If salty or dirty water is pumped, it is recommended to clean the impeller in the pump with clean water.
該設(shè)備維修前,請關(guān)閉點火開關(guān)并斷開任意電池線路或取出電池。當(dāng)發(fā)動機閑置時:(1)請勿放置在上方放置重物或物體。(2)請勿從任何高處拋落。更多注意事項就來我們網(wǎng)站
http://m.xintli.net咨詢吧!
Before the equipment is repaired, please turn off the ignition switch and disconnect any battery lines or take out the battery. When the engine is idle: (1) Do not place heavy objects or objects on it. (2) Do not drop from any height. More notes on our website http://m.xintli.net Consult!