消防水炮驗收的一般規定以及布置
來源:http://m.xintli.net/ 日期:2022-11-10
消防水炮是噴射水,遠距離撲救一般固體物質的消防設備,下面
川消小編就來講講消防水炮驗收的一般規定以及布置吧。
The fire water monitor is a fire-fighting equipment that sprays water and remotely fights ordinary solid substances. Now let's talk about the general regulations and arrangement of fire water monitor acceptance.
消防水炮驗收的一般規定
General provisions for acceptance of fire water monitor
供水管道應與生產、生活用水管道分開。
Water supply pipes shall be separated from production and domestic water pipes.
供水管道不宜與泡沫混合液的供給管道合用。寒冷地區的濕式供水管道應采取防凍保護措施,干式管道應設排除管道內積水和空氣的設施。管道設計應滿足設計流量、壓力和開啟噴射的時間等要求。
The water supply pipeline should not be used together with the supply pipeline of foam mixture. Anti freezing protection measures shall be taken for wet water supply pipes in cold areas, and facilities for removing water and air from the pipes shall be set for dry pipes. The pipe design shall meet the requirements of design flow, pressure and time from opening to spraying.
消防水源的容量不應小于規定滅火時間和冷卻時間內需要同時使用水炮、泡沫炮、保護水幕噴頭等用水量及供水管道內充水量之和。該容量可減去規定滅火時間和冷卻時間內補充的水量。
The capacity of fire water source shall not be less than the sum of water consumption of water monitor, foam monitor, protective water curtain nozzle and water filling in the water supply pipeline within the specified fire extinguishing time and cooling time. This capacity can be reduced by the amount of water replenished during the specified fire extinguishing time and cooling time.
消防水泵的供水壓力應能滿足系統中水炮、泡沫炮噴射壓力的要求。
The water supply pressure of the fire pump shall meet the requirements of the spray pressure of the water monitor and foam monitor in the system.

滅火劑及加壓氣體的補給時間不宜大于48h。
The supply time of fire extinguishing agent and pressurized gas shall not be longer than 48h.
水炮系統和泡沫炮系統從啟動泡沫噴射水或泡沫的時間不應大于5min,干粉炮系統從啟動炮口噴射干粉的時間不應大于2min。
The time from the start of the water monitor system and the foam monitor system to the foam water or foam injection shall not be more than 5min, and the time from the start of the dry powder monitor system to the muzzle dry powder injection shall not be more than 2min.
消防水炮驗收的布置
Arrangement of fire water monitor acceptance
室內消防水炮的布置數量不應少于兩門,其布置高度應保證消防炮的射流不受上部建筑結構件的影響,并應能使兩門水炮的水射流同時到達被保護區的任一部份。室內系統應采用濕式給水系統,消防炮位處應設置消防水泵啟動按鈕。
The number of indoor fire water monitors shall not be less than two, and their arrangement height shall ensure that the jet of fire monitors is not affected by the superstructure structure, and the jet of two water monitors can reach any part of the protected area at the same time. The indoor system shall adopt the wet water supply system, and the fire pump start button shall be set at the fire gun position.
設置消防炮平臺時,其結構強度應能滿足消防炮噴射反作用力的要求,結構設計應能滿足消防炮正常使用要求。
When the fire monitor platform is set, its structural strength shall meet the requirements of the reaction force of the fire monitor, and the structural design shall meet the requirements of the normal use of the fire monitor.
室外消防炮的布置應能使消防炮射流完全覆蓋被保護場所及被保護物,且應滿足滅火強度及冷卻強度的要求。
The outdoor fire monitor shall be arranged so that the fire monitor jet can completely cover the protected place and objects, and shall meet the requirements of fire extinguishing intensity and cooling intensity.
消防炮應設置在被保護場所常年主導風向的上風向;
The fire monitor shall be set in the upwind direction of the perennial dominant wind direction of the protected place;
當滅火對象高度較高、面積較大時,或在消防炮的射流受到較高大障礙物的阻擋時,應設置消防炮塔。
When the fire extinguishing object is high and large, or when the jet of the fire monitor is blocked by high and large obstacles, the fire turret shall be set.
This is the end of the general regulations on acceptance of fire water monitors and the layout. If you have anything to say about this, you can come to our website at any time http://m.xintli.net Consult!