當發生火災時,消防車的水泵可迅速方便地通過該接合器的接口與建筑物內的消防設備相連接,并送水加壓,從而使室內的消防設備得到充足的壓力水源,用以撲滅不同樓層的火災。下面
川消小編來講講消防水泵接合器的施工安裝與執行標準。
In case of fire, the water pump of the fire truck can quickly and conveniently connect with the fire fighting equipment in the building through the interface of the adapter, and send water for pressurization, so that the indoor fire fighting equipment can get sufficient pressure water source to put out the fire in different floors. Next, Sichuan Xiaobian will talk about the construction, installation and executive standards of fire pump adapter.
施工安裝
Construction and installation
1)統一規定試驗壓力為工作壓力的1.5倍,但不得小于0.6MPa。既便于驗收時掌握,也滿足工程需要。
1) It is uniformly stipulated that the test pressure is 1.5 times of the working pressure, but not less than 0.6MPa. It is not only easy to master during acceptance, but also meet the needs of the project.
2)為保證管道暢通,防止雜質焊渣等損壞消火栓,消防管道應進行沖洗。
2) In order to ensure smooth pipeline and prevent foreign welding slag from damaging the fire hydrant, the fire pipeline shall be flushed.
3)消防水泵接合器的閥應進行定壓(定壓值應由設計給定),定壓后的系統應能保證高處的一組消火栓的水栓能有10~15m的充實水柱。
3) The safety valve of the fire pump adapter shall be subject to constant pressure (the constant pressure value shall be given by the design), and the system after constant pressure shall ensure that the hydrants of a group of fire hydrants at high places can have a full water column of 10-15m.
4)因栓口直接設在建筑物外墻上,操作時必然緊靠建筑物,為保證消防人員的操作,故強調上方須有防墜落物打擊的措施。
4) Since the hydrant port is directly set on the external wall of the building, it must be close to the building during operation. In order to ensure the operation safety of fire fighters, it is emphasized that there must be measures to prevent falling objects from hitting above.

執行標準
Executive standards
1)工程標準
1) Engineering Standards
《建筑設計防火規范》【2018年版】GB50016-2014
Code for Fire Protection Design of Buildings [2018 Edition] GB50016-2014
《消防給水及消火栓系統技術規范》GB50974-2014
Technical Code for Fire Water Supply and Hydrant Systems GB50974-2014
《建筑給水排水及采暖工程施工質量驗收規范》GB50242-2002
Code for Acceptance of Construction Quality of Building Water Supply Drainage and Heating Engineering GB50242-2002
2)99S203消防水泵接合器安裝
2) Installation of 99S203 fire pump adapter
The fire pump adapter effectively solves the problem that it is difficult for the fire truck to extinguish the fire or the indoor fire equipment cannot extinguish the fire due to insufficient pressure water source after the building fires. Come to our website if you need http://m.xintli.net Consult and understand!