川消室外消防栓布置的消防要求
來源:http://m.xintli.net/ 日期:2023-01-30
在住宅小區、在公園里、在馬路邊隨處可見消防栓,它的作用是火源,降低著火點和隔絕助燃物。而消火栓分為室內消防栓和室外消防栓,是保護消防的不可或缺的消防設備之一,那么室外消防栓安裝規范要求有哪些?與
川消小編一起來看下吧。
Fire hydrants can be seen everywhere in residential areas, parks, and roads. Their function is to eliminate the fire source, reduce the ignition point and isolate combustion-supporting materials. Fire hydrants are divided into indoor fire hydrants and outdoor fire hydrants, which are one of the indispensable fire fighting equipment to protect fire safety. What are the requirements of the installation specifications for outdoor fire hydrants? Let's have a look with Sichuan Xiaobian.
1.基本的要求就是室外消防栓應該安裝在明顯的位置,并且還要出水方便,這樣急救滅火的時候才不會耽誤時間。在氣候溫暖的地面安裝地上式消防栓,在氣候寒冷地面安裝地下式消防栓,地下式消防栓還需要在地面設置安裝固定的標志。
1. The basic requirement is that the outdoor fire hydrant should be installed in an obvious position, and it should be convenient to get out of the water, so that the time will not be delayed in the emergency fire fighting. The aboveground fire hydrant shall be installed on the ground with warm climate, and the underground fire hydrant shall be installed on the ground with cold climate. The underground fire hydrant shall also be installed with fixed signs on the ground.
2.居住區或市政府的室外消防栓應該沿著道路安裝,當道路超過60m時,應該要在道路兩旁設置,并且要靠近十字路口。室外消火栓的設置間隔不應該大于120m,距離道路邊緣不能超過2m,距離建筑外墻不能小于5m,如果是高層建筑,距離外墻不能大于40m,距離一般建筑外墻不能大于150m。
2. Outdoor fire hydrants in residential areas or municipal governments should be installed along the road. When the road is more than 60m, they should be installed on both sides of the road and close to the intersection. The setting interval of outdoor fire hydrant shall not be more than 120m, the distance from the road edge shall not be more than 2m, and the distance from the external wall of the building shall not be less than 5m. For high-rise buildings, the distance from the external wall shall not be more than 40m, and the distance from the external wall of general buildings shall not be more than 150m.

3.工業企業單位的室外消防栓應該在工藝裝置區、儲罐區這些裝置的周圍安裝設置,間距不應該大于60m,如工藝裝置區,如果裝置的寬度大于120m,應該在裝置的周圍適當增加消防栓,對于儲罐區,消防栓應設置在防火堤外,且儲罐區消防栓的可使用范圍應大于15m,否則不算入可使用的范圍之內。消防栓的栓口直徑規范大小為150m。
3. The outdoor fire hydrants of industrial enterprises should be installed around the process unit area and storage tank area, and the spacing should not be greater than 60m. For example, in the process unit area, if the width of the device is greater than 120m, the fire hydrants should be appropriately added around the device. For the storage tank area, the fire hydrants should be set outside the fire dike, and the usable range of the fire hydrants in the storage tank area should be greater than 15m, otherwise they should not be included in the usable range. The diameter of fire hydrant mouth is 150 m.
4.室外消防栓的數量應根據它保護的范圍、流量和用量進行綜合計算,每一只消防栓的流量是10~15L/S。對于高層建筑,室外消防栓的保護大范圍是40m,對于多層建筑,室外消防栓的保護范圍在150m之內,如果所需要的消防栓流量不大于15L/S時,還可以不用設置室外消防栓,僅用室內消防栓就可以了。
4. The number of outdoor fire hydrants shall be comprehensively calculated according to its protection scope, flow and consumption. The flow of each fire hydrant is 10-15L/S. For high-rise buildings, the protection range of outdoor fire hydrants is 40m, and for multi-storey buildings, the protection range of outdoor fire hydrants is within 150m. If the required flow of fire hydrants is not more than 15L/S, outdoor fire hydrants can not be set, only indoor fire hydrants can be used.
在發生火災的時候,它可以急救滅火,拯救生命。按規定室外消防栓的水不得擅用,每年少檢查一次。曾大家可以對照以上室外消防栓安裝規范詳細說明,看看自己身邊的室外消防栓安裝是否規范。更多相關內容就來我們網站
http://m.xintli.net咨詢吧!
In case of fire, it can give first aid to extinguish the fire and save lives. According to the regulations, the water of outdoor fire hydrants shall not be used without authorization, and shall be inspected at least once a year. You can refer to the above specifications for the installation of outdoor fire hydrants to see if the installation of outdoor fire hydrants around you is standard. Come to our website for more relevant content http://m.xintli.net Ask!