    泡沫滅火系統的調試應符合什么規定?

    來源:http://m.xintli.net/ 日期:2023-05-22

    (1)當為手動滅火系統時,應以手動控制的方式進行一次噴水試驗;當為自動滅火系統時,應以手動和自動控制的方式各進行一次噴水試驗,系統流量、泡沫產生裝置的工作壓力、比例混合裝置的工作壓力、系統的響應時間均應達到設計要求。
    (1) When using a manual fire extinguishing system, a water spray test should be conducted in a manually controlled manner; In case of an automatic fire extinguishing system, a water spray test shall be carried out manually and automatically. The system flow, the working pressure of the foam generating device, the working pressure of the proportioning device, and the response time of the system shall all meet the design requirements.
    檢查數量:當為手動滅火系統時,選擇遠的防護區或儲罐;當為自動滅火系統時,選擇所需泡沫混合液流量大和遠的兩個防護區或儲罐分別以手動和自動的方式進行試驗。
    Inspection quantity: When using a manual fire extinguishing system, select a remote protective area or storage tank; In case of automatic fire extinguishing system, two protection areas or storage tanks with large and far foam mixture flow shall be selected for test in manual and automatic ways respectively.
    (2)川消小編提醒,低倍數泡沫滅火系統按本條第1款的規定噴水試驗完畢,將水放空后進行噴泡沫試驗;當為自動滅火系統時,應以自動控制的方式進行;噴射泡沫的時間不宜小于1min;實測泡沫混合液的流量、發泡倍數及到達遠防護區或儲罐的時間應符合設計要求,混合比不應低于所選泡沫液的混合比。
    (2) Sichuan Xiaobian reminds that the low expansion foam fire extinguishing system has completed the water spraying test according to the provisions of paragraph 1 of this article, and the foam spraying test is conducted after the water is emptied; When it is an automatic fire extinguishing system, it should be carried out in an automatic control manner; The time of spraying foam should not be less than 1min; The measured flow, foaming ratio and time to reach the far protection area or storage tank of foam mixture shall meet the design requirements, and the mixing ratio shall not be lower than that of the selected foam mixture.
    川消
    檢查數量:選擇遠的防護區或儲罐,進行一次試驗。
    Inspection quantity: Select a remote protective area or storage tank for one test.
    (3)中倍數、高倍數泡沫滅火系統按本條第1款的規定噴水試驗完畢,將水放空后進行噴泡沫試驗,當為自動滅火系統時,應以自動控制的方式對防護區進行噴泡沫試驗,噴射泡沫的時間不宜小于30S,實測泡沫供給速率及自接到火災模擬信號開始噴泡沫的時間應符合設計要求,混合比不應低于所選泡沫液的混合比。
    (3) The medium and high expansion foam fire extinguishing systems shall be sprayed with foam after the completion of water spraying test according to the provisions of paragraph 1 of this article. In case of automatic fire extinguishing systems, foam spraying test shall be carried out in the protection area in an automatic control manner. The time of foam spraying shall not be less than 30s. The measured foam supply rate and the time from receiving the fire simulation signal to starting to spray foam shall meet the design requirements, The mixing ratio shall not be lower than that of the selected foam concentrate.
    檢查數量:全數檢查。
    Inspection quantity: All inspections.
    泡沫滅火系統的調試應符合以上所講內容規定,希望對您有所幫助,更多事項就來我們網站http://m.xintli.net留言咨詢吧!
    The commissioning of the foam fire extinguishing system should comply with the above provisions. I hope it will be helpful to you. For more information, please come to our website http://m.xintli.net Leave a message for consultation!
    上一篇:自動跟蹤定位射流滅火系統應符合這樣的要求!
    下一篇:川消自動噴水滅火設備故障的5個常見原因

    相關產品 / Related products

    无码中文字幕日韩专区| 久久人妻无码中文字幕| 色综合久久最新中文字幕| 久久久无码一区二区三区| 精品久久久久久无码中文野结衣| 国产成人无码一区二区三区 | 亚洲精品无码久久久久| 亚洲av中文无码乱人伦在线r▽| 日韩免费人妻AV无码专区蜜桃| 五月婷婷在线中文字幕观看 | 91久久精品无码一区二区毛片 | 丰满日韩放荡少妇无码视频| 中文字幕人妻色偷偷久久| 国内精品人妻无码久久久影院| 无码av高潮喷水无码专区线| 亚欧成人中文字幕一区| 亚洲AV无码资源在线观看| 成?∨人片在线观看无码| 亚洲大尺度无码专区尤物| 中文字幕51日韩视频| 日韩人妻无码精品无码中文字幕| 国色天香中文字幕在线视频| 久久久久亚洲AV无码专区桃色| 十八禁无码免费网站| 亚洲av无码不卡| 亚洲成AV人在线观看天堂无码| 中文字幕人妻无码一区二区三区| 一二三四在线播放免费观看中文版视频| 亚洲中文字幕在线观看| 久久精品aⅴ无码中文字字幕不卡| 亚洲国产精品无码久久青草 | 免费无码成人AV在线播放不卡| 一本色道无码道在线观看| 中文字幕无码日韩专区免费| 少妇无码太爽了不卡在线观看 | 中文无码字慕在线观看| 日本欧美亚洲中文| 亚洲日韩在线中文字幕第一页| 日韩中文字幕在线不卡| 欧洲精品无码一区二区三区在线播放| 亚洲看片无码在线视频|