川消消防水炮現場控制箱安裝注意事項
來源:http://m.xintli.net/ 日期:2022-05-15
消防水炮現場控制箱的作用就是切換水炮的工作模式,然后就是手動來進行電磁閥的開和閉,當然還有就是關閉報警裝置,但是對于消防水炮現場控制箱在安裝的時候,要注意什么事項?
The function of the on-site control box of the fire water monitor is to switch the working mode of the water monitor, and then manually open and close the solenoid valve. Of course, it also turns off the alarm device. But what should be paid attention to when installing the on-site control box of the fire water monitor?
川消消防水炮現場控制箱在墻壁上安裝時,其底邊距地(樓)面高度不應小于1.5m,其靠近門軸的側面距墻不應小于0.5m,正面操作距離不應小于1.2m;當安裝在輕質墻上時,應采取加固措施。
When the field control box of Chuanxiao fire monitor is installed on the wall, the height from its bottom edge to the ground (floor) surface shall not be less than 1.5m, the side near the door shaft shall not be less than 0.5m from the wall, and the front operation distance shall not be less than 1.2m; When installed on light wall, reinforcement measures shall be taken.
消防水炮現場控制箱應安裝牢固,不得傾斜。消防水炮現場控制箱及配線金屬管或線槽應做接地保護,接地應牢固,并有明顯標志。
The on-site control box of fire water monitor shall be installed firmly without inclination. The on-site control box and wiring metal pipe or trunking of fire water monitor shall be grounded for protection. The grounding shall be firm and clearly marked.
進入的電纜或導線,應符合下列要求:
Incoming cables or conductors shall meet the following requirements:
配線整齊,避免交叉,并應固定牢固;電纜芯線和所配導線的端部均應標明編號,并與圖紙一致,字跡清晰不易褪色;端子板的每個接線端,接線不得超過2根;
The wiring shall be neat, avoid crossing, and shall be fixed firmly; The ends of cable cores and wires shall be marked with numbers, which shall be consistent with the drawings, and the handwriting shall be clear and not easy to fade; Each terminal of the terminal board shall not have more than 2 wires;

電纜芯和導線,應留有適當余量;導線引入線穿線后,金屬管或金屬線槽與控制箱的接口處應做封堵;
Appropriate allowance shall be reserved for cable core and conductor; After the lead-in wire is threaded, the interface between the metal pipe or metal trunking and the control box shall be blocked;
控制箱的電源引入線,應直接與消防電源連接,嚴禁使用電源插頭,電源引入線應有明顯標志。消防水炮現場控制箱在安裝前,應進行功能檢查,避免安裝運輸過程造成損壞的設備。
The power lead-in line of the control box shall be directly connected with the fire power supply. It is strictly prohibited to use the power plug. The power lead-in line shall be clearly marked. Before installation, the on-site control box of fire water monitor shall be subject to functional inspection to avoid the installation of equipment damaged during transportation.
嚴禁帶電拆裝各電源連接線和信號線。消防水炮現場控制箱的安裝和維修過程均應斷電操作。消防水炮現場控制箱的外殼、電源部分和外接導線的金屬軟管應作保護接地。
It is strictly prohibited to disassemble and assemble all power connecting wires and signal wires with electricity. The on-site control box of fire water monitor shall be powered off during installation and maintenance. The shell, power supply part and metal hose of external conductor of on-site control box of fire water monitor shall be grounded for protection.
川消消防水炮現場控制箱安裝注意事項就是以上相關內容了,川消生產制作有關消防器材多年,實力值得信任,快來關注網站
m.xintli.net了解吧。
The precautions for the installation of on-site control box of Chuanxiao fire water monitor are related to the above contents. Chuanxiao has specialized in producing relevant fire-fighting equipment for many years, and its strength is trustworthy. Please pay attention to the website www.cx-fire See. Com.