每季度應對川消氣體滅火系統進行1次綜合檢查
來源:http://m.xintli.net/ 日期:2022-12-31
每季度應對氣體滅火系統進行1次綜合檢查,并應符合下列規定,接下來
川消小編為您解答。
The gas fire extinguishing system should be comprehensively inspected once a quarter, and should comply with the following regulations. Next, Sichuan Xiaobian will answer for you.
1 可燃物的種類、分布情況,防護區的開口情況,應符合設計規定。
1. The type and distribution of combustibles and the opening of the protection area shall meet the design requirements.
2 儲存裝置間的設備、滅火劑輸送管道和支、吊架的固定,應無松動。
2 The equipment, fire extinguishing agent delivery pipeline, supports and hangers between storage devices shall be fixed without looseness.
3 連接管應無變形、裂紋及老化。必要時,送法定質量檢驗機構進行檢測或更換。
3 The connecting pipe shall be free from deformation, crack and aging. If necessary, it shall be sent to the statutory quality inspection agency for inspection or replacement.
4 各噴嘴孔口應無堵塞。
4 Nozzle orifices shall be free from blockage.
5 對高壓二氧化碳儲存容器逐個進行稱重檢查,滅火劑凈重不得小于設計儲存量的90%。
5 Weigh and check the high-pressure carbon dioxide storage containers one by one, and the net weight of extinguishing agent shall not be less than 90% of the designed storage capacity.

6 滅火劑輸送管道有損傷與堵塞現象時,應按本規范第E.1節的規定進行嚴密性試驗和吹掃。
6 If the fire extinguishing agent delivery pipeline is damaged or blocked, the tightness test and purging shall be carried out according to the provisions of Section E.1 of this specification.
每年應按本規范第E.2節的規定,對每個防護區進行1次模擬啟動試驗,并應按本規范第7.4.2條規定進行1次模擬噴氣試驗。
Each protection area shall be subject to one simulated start test every year according to the provisions of Section E.2 of this specification, and one simulated air injection test shall be conducted according to the provisions of Article 7.4.2 of this specification.
低壓二氧化碳滅火劑儲存容器的維護管理應按《壓力容器技術監察規程》執行;鋼瓶的維護管理應按《氣瓶監察規程》執行。滅火劑輸送管道耐壓試驗周期應按《壓力管道管理與監察規定》執行。
The maintenance and management of storage containers for low pressure carbon dioxide extinguishant shall be carried out in accordance with the Supervision Regulation on Safety Technology for Pressure Vessels; The maintenance and management of steel cylinders shall be carried out in accordance with the Gas Cylinder Safety Supervision Regulation. The pressure test cycle of the fire extinguishing agent transmission pipeline shall be in accordance with the Regulations on Safety Management and Supervision of Pressure Pipeline.
So is the above answer to the question of conducting a comprehensive inspection of the gas fire extinguishing system once a quarter helpful to you? Come to our website for more information http://m.xintli.net Consult!