氣體滅火系統(tǒng)投入使用要記得每月進行檢查
來源:http://m.xintli.net/ 日期:2022-12-31
氣體滅火系統(tǒng)投入使用時,要記得每月進行定期檢查,每月檢查應符合下列要求,下面
川消小編為您解答。
When the gas fire extinguishing system is put into use, remember to conduct regular inspection every month. The monthly inspection should meet the following requirements. The following section of Chuanxiao will answer for you.
應按檢查類別規(guī)定對氣體滅火系統(tǒng)進行檢查,并按本規(guī)范表F做好檢查記錄。檢查中發(fā)現(xiàn)的問題應及時處理。
The gas fire extinguishing system shall be inspected according to the inspection category, and inspection records shall be made according to Table F of this specification. Problems found in the inspection shall be handled in a timely manner.
每日應對低壓二氧化碳儲存裝置的運行情況、儲存裝置間的設備狀態(tài)進行檢查并記錄。
The operation of the low pressure carbon dioxide storage device and the equipment status between the storage devices shall be checked and recorded daily.
每月檢查應符合下列要求:
The monthly inspection shall meet the following requirements:
1 低壓二氧化碳滅火系統(tǒng)儲存裝置的液位計檢查,滅火劑損失10%時應及時補充。
1. Check the liquid level gauge of the storage device of the low pressure carbon dioxide fire extinguishing system, and replenish it in time when the extinguishing agent loses 10%.
2 高壓二氧化碳滅火系統(tǒng)、七氟丙烷管網(wǎng)滅火系統(tǒng)及IG541滅火系統(tǒng)等系統(tǒng)的檢查內容及要求應符合下列規(guī)定:
2 The inspection contents and requirements of high-pressure carbon dioxide fire extinguishing system, heptafluoropropane pipe network fire extinguishing system, IG541 fire extinguishing system and other systems shall meet the following requirements:

1) 滅火劑儲存容器及容器閥、單向閥、連接管、集流管、泄放裝置、選擇閥、閥驅動裝置、噴嘴、信號反饋裝置、檢漏裝置、減壓裝置等全部系統(tǒng)組件應無碰撞變形及其他機械性損傷,表面應無銹蝕,保護涂層應完好,銘牌和標志牌應清晰,手動操作裝置的防護罩、鉛封和標志應完整。
1) Fire extinguishing agent storage containers and all system components such as container valves, one-way valves, connecting pipes, collecting pipes, safety relief devices, selector valves, valve driving devices, nozzles, signal feedback devices, leak detection devices, pressure relief devices, etc. shall be free of collision deformation and other mechanical damage, the surface shall be free of rust, the protective coating shall be intact, the nameplates and signboards shall be clear, and the protective covers, lead seals and safety signs of manual operating devices shall be complete.
2) 滅火劑和驅動氣體儲存容器內的壓力,不得小于設計儲存壓力的90%。
2) The pressure in the fire extinguishing agent and driving gas storage container shall not be less than 90% of the design storage pressure.
3 預制滅火系統(tǒng)的設備狀態(tài)和運行狀況應正常。
3 The equipment status and operation status of prefabricated fire extinguishing system shall be normal.
The gas fire extinguishing system shall be regularly inspected and maintained by a full-time person who has received special training and passed the examination. Come to our website if you have any questions http://m.xintli.net Consult!